Network Outputs cannot be discovered from FX controllers running 12.0.1 firmware that are mapped as General BACnet Devices.
Problem
It is not possible to auto-discover network outputs on controllers running 12.0.1 firmware when they are mapped as General BACnet Devices. Firmware 12.0.1 contains a bug that prevents network output and internal points from being auto-discovered
Affects
■ F4-CGM09090-0
■ F4-CGM09090-0H
■ F4-CGM04060-0
■ F4-CGE09090-0
■ F4-CGE09090-0H
■ F4-CGE04060-0
■ F4-CCM09090-0
■ F4-CVM03050-0
■ F4-CVM03050-0P
■ F4-CVE03050-0P
■ FX-PCV1930-0
■ FX-PCA4911-0
■ FX-PCA3613-0
■ CH-PCA4911-0
■ CH-PCA3613-0
■ CH-PCA2513-0
■ CH-PCV1930-0
■ LC-ATC1510-0
Note: This also affects Buy American compliant models with product codes that end in -xG
Workaround
Do not install firmware 12.0.1 on the affected Field Controllers. You can manually map Bacnet exposed network outputs and internal points in the controller application into the FX or third party supervisory device. This issue is not present in the 12.0.0.373 firmware.
Solution
The upcoming firmware patch 12.0.2 will resolve this issue.
Network Outputs cannot be discovered from FX controllers running 12.0.1 firmware
Tags: Johnson controls