616W-2-LCD: Differential pressure transmitter, range 0-6" w.c., max. pressure 5 psig.
Description
Additional Product Details
ositive, negative and differential pressures can be measured within a full span accuracy of 0.25 with the SERIES 616W Differential Pressure Transmitter. Units are enclosed in a polycarbonate case, rated NEMA 4X (IP66) and operate by sensing the pressure of air and compatible gases then sending a standard 4-20 mA output signal. Design enables operation in 2-wire current loops. A wide range of models are available factory calibrated to specific ranges. The span and zero controls are for use when checking calibration. They are not intended for re-ranging to a significantly different span. The LCD display allows local indication of pressure.